What
is the difference between CCA and RC?
A good battery needs high CCA and high capacity readings but these attributes
reflect differently depending on the application. A high CCA reading
assures good battery conductivity and provides strong cranking ability.
High CCA goes hand-in-hand with a low internal battery resistance. Figure
1 compares high CCA with a large, open tap that allows unrestricted
flow.
| |
|
Figure
1: Battery with high CCA and 100% reserve capacity.
A high CCA battery can be compared to a large, open tap that allows
unrestricted flow. |
Reserve
capacity governs the amount of energy the battery can store. A new battery
is rated at a nominal capacity of 100%. As the battery ages, the reserve
capacity drops and the battery eventually needs replacing when the reserve
capacity falls below 70%. The RC reading always refers to a fully charged
battery; the state-of-charge (SoC) should not affect the readings when
measured with a rapid-tester.
A battery may provide a good CCA reading and start a car well but be
low on reserve capacity. This battery would be run down in no time when
drawing auxiliary power. Figure 2 illustrates such a battery. The so-called
'rock content' that builds up as the battery ages is permanent and cannot
be reversed.
|
|
Figure
2: Battery with high CCA but low reserve capacity.
The cranking on this battery is good but running on auxiliary power
will drain the battery quickly. |
Figure
3 illustrates a battery with good reserve capacity but low CCA. This
battery has a difficult task turning the starter and needs replacing
even though it could be used for low load applications.
|
|
Figure
3: Battery with low CCA but high reserve capacity.
The low CCA of this battery provides poor cranking although the
reserve capacity is high. |
Capacity
measurements, the most comprehensive battery test
With increased demand for auxiliary power on vehicles, measuring energy
reserve is more relevant than CCA. The slogan goes: "Starting is
easy
but can I steer and brake?" Modern battery testers must
adapt to this new requirement and also include RC measurement. European
car manufacturers place heavy emphasis on reserve capacity, while in
North America CCA is still the accepted standard to assess battery performance.
Most modern battery testers also provide state-of-charge readings (SoC).
Measuring reserve capacity is more complex than CCA. Many methods have
been tried, including multi-frequency conductance, but most have limitations.
One of the main obstacles is processing large volumes of data received
when scanning a battery with multiple frequencies. Collecting the data
is easy; making practical use of the information is the problem. The
cost of high-speed microprocessors and processing difficulties has put
the price tag on such battery testers out of range. Put changes are
coming.
Cadex Electronics has developed a method that enables the processing
of a large volume of data received through multi-model electro-chemical
impedance spectroscopy (EIS). Trademarked Spectro, the system
injects 24 excitation frequencies ranging from 20 to 2000 Hertz. The
signals are regulated at 10mV to remain within the thermal battery voltage
of lead acid. This permits stable readings for small and large batteries.
The test takes 20 seconds, during which about 40 million transactions
are completed.
Normally, EIS requires dedicated equipment and a computer to analyze
the obtained data. To permit such analyses in a hand held unit, high-speed
digital signal processing is used. In 2005, the Spectro invention
received a patent (US patent 6,778,913, Jörn Tinnemeyer).
Spectro has primarily been demonstrated on 12V lead-acid batteries,
automotive in particular. The large pool of available car batteries
provides an excellent platform to verify the technology. The same technology
can also be used on nickel and lithium-based batteries.
On the strength of our invention, Cadex has developed a battery rapid-tester
(CA-12) for automotive batteries. One of the strongest features of Spectro
is its ability to reveal CCA, reserve capacity and state-of-charge on
a single measurement. Displaying RC has been on the wish list of battery
manufacturers and service centers for many years. In fact, this will
be the first time such information can be obtained non-invasively with
a commercial hand-held tester. Figure 4 shows the suggested display
format.
 |
 |
Figure
4: Displays CCA, RC and SoC.
During the 20-second test time, the digital signal processor completes
40 million transactions. |
The battery
needs to be charged for testing. The typical test band is 50% to 100%
SoC. Early tests provide stable results over a wide temperature range.
There is good immunity to electrical noise. Parasitic loads of up to
30A have been tried without notable side effects. Furthermore, Spectro
appears to be less sensitive to surface charge than single frequency
AC conductance and the CCA readings are more consistent. The tester
tolerates some acid stratification but chemical additives may affect
the readings. Figure 5 illustrates the CA-12 tester.
|
|
Figure
5: Rendering of the Cadex CA-12 battery rapid-tester.
The test results are available in most global standards. The RC
can be shown as a percentage of the nominal capacity or in discharge
time. |
Early
test results on Reserve Capacity
Verifying the accuracy and repeatability of a new invention takes much
time and effort. To test Spectro, Cadex assembled a test bed of
91 car batteries with diverse performance levels. The preparation consisted
of a fully saturated charge, followed by a 24-hour rest period and a
25A discharge to 10.50V (1.75V/cell), during which the reserve capacity
was measured. This procedure produced an astonishing +/-15% variation
in capacity readings across the full population. When comparing the
capacity obtained through a conventional discharge and by non-invasive
means, one must take into account the vulnerability of lead acid in
producing varied readings even when using highly accurate charges and
load banks.
Figure 6 compares the reserve capacities of 38 randomly chosen car batteries.
The black diamonds show the reserve capacity derived through a full
discharge; the purple squares represent Spectro estimations using
a generic matrix.
|
|
Figure
6: RC comparison of 38 batteries with a generic matrix.
The black diamonds show the RC obtained with a full discharge; the
purple squares represent Spectro estimations. |
How can
the RC readings be further improved? Best results are achieved by sorting
the batteries according to architecture and CCA rating. We developed
a model specific matrix and tested a group of same-model batteries.
Figure 7 shows the reserve capacity readings derived through a conventional
full discharge and Spectro. With specific matrices, the readings
approach laboratory standards in terms of accuracy.
 |
Figure
7: RC comparison of 24 batteries with a model-specific matrix.
The purple squares (Spectro) followthe black diamonds very
closely. Specific matrices approach reading within laboratory standards. |
Although
the test results in Figure 6, and in particular Figure 7, look very
encouraging, we need to be reminded that Spectro is not a universal
battery tester capable of measuring any battery that comes along. It
cannot be compared to a photocopier that duplicates any document or
flat object by simply pressing the copy button. Rather, Spectro
needs a battery specific matrix as a reference. To a large extent, the
quality of the matrix governs the accuracy. The matrices are stored
in the tester and need selecting together with the Ah and/or CCA rating.
We are currently making gains in establishing generic matrices that
may be used for CCA and RC measurements.
Price is another issue. Because of added complexity and higher parts
count compared to single frequency AC conductance, the Spectro
technology will command a higher price. We are not competing directly
with currently available battery testers; rather, we offer a solution
for those needing a better technology because the present method may
be insufficient.
Summary
Technology has advanced to a point where measuring battery performance
through non-invasive means will become the acceptable standard. Applying
a full discharge for the purpose of obtaining the reserve capacity is
impractical and stresses the battery. Multi-model electrochemical impedance
spectroscopy with improved data processing algorithms will bring this
task one step closer to reality.
Multi-frequencies EIS not only makes RC estimations possible; it also
improves the CCA readings. Rather than providing a reference numbers
relating to battery conductivity, EIS can give actual CCA equivalents.
The technology also improves state-of-charge estimations. Typical applications
include verifications of battery warranty returns, assessing the state-of-life
of stationary batteries and checking the capacity for batteries in defense
and marine applications. EIS is also an indispensable tool in examining
batteries for wheelchair, golf carts, robots, boats and forklifts.