| |
Charging the lead-acid battery
(BU13)
The charge algorithm for lead-acid batteries is similar to lithium-ion
but differs from nickel-based chemistries in that voltage rather than
current limiting is used. The charge time of a sealed lead-acid battery
is 12-16 hours (up to 36 hours for larger capacity batteries). With
higher charge currents and multi-stage charge methods, the charge
time can be reduced to 10 hours or less. Lead-acid cannot be fully
charged as quickly as nickel or lithium-based systems.
It takes about 5 times as long to recharge a lead-acid battery to
the same level as it does to discharge. On nickel-based batteries,
this ratio is 1:1, and roughly 1:2 on lithium-ion.
A multi-stage charger first applies a constant current charge, raising
the cell voltage to a preset voltage (Stage 1 in Figure 1). Stage
1 takes about 5 hours and the battery is charged to 70%. During the
topping charge in Stage 2 that follows, the charge current is gradually
reduced as the cell is being saturated. The topping charge takes another
5 hours and is essential for the well being of the battery. If omitted,
the battery would eventually lose the ability to accept a full charge.
Full charge is attained after the voltage has reached the threshold
and the current has dropped to 3% of the rated current or has leveled
off. The final Stage 3 is the float charge, which compensates for
the self-discharge.
| |  | Figure
1: Charge stages of a lead-acid battery. The battery charges at a constant
current to a set voltage threshold (Stage 1). As the battery saturates, the current
drops (Stage 2). The float charge compensates for the self-discharge (Stage 3). |
Correct
settings of the voltage limits are critical and range from 2.30V to 2.45V. Setting
the voltage limit is a compromise. On one end, the battery wants to be fully charged
to get maximum capacity and avoid sulfation on the negative plate. A continually
over-saturated condition at the other end, however, would cause grid corrosion
on the positive plate. It also promotes gassing, which results in venting and
loss of electrolyte. The voltage limit shifts with temperature. A higher
temperature requires slightly lower voltages and vice versa. Chargers that are
exposed to large temperature fluctuations should be equipped with temperature
sensors to to adjust the charge voltage for optimum charge. Figure 2 compares
the advantages and limitations of various peak voltage settings.
| |  | Figure
2: Effects of charge voltage on a small lead-acid battery (SLA). Cylindrical
lead-acid cells have higher voltage settings but are lower for VRLA and car batteries. |
The
battery cannot remain at the peak voltage for too long; the maximum allowable
time is 48 hours. When reaching full charge, the voltage must be lowered to maintain
the battery at between 2.25 and 2.27V/cell. Manufacturers of large lead-acid batteries
recommend a float charge of 2.25V at 25°C.
Car batteries and valve-regulated-lead-acid
batteries (VRLA) are typically charged to between 2.26 and 2.36V/cell. At 2.37V,
most lead-acid batteries start to gas, causing loss of electrolyte and possible
temperature increases. The exceptions are small sealed lead acid batteries (SLA),
which can be charged to 2.50V/cell without adverse side effect.
The cylindrical
Cyclone by Hawker requires a very high peak voltage of 2.60V/cell. Failing to
apply the recommended voltage threshold causes a gradual decrease in capacity
due to sulfation. Follow manufacturer's recommended settings on these lead-acid
variations.
Large VRLA batteries are often charged with a float-charge
current to 2.25V/cell. A full charge may take several days. It is interesting
to observe that the current in float charge mode gradually increases as the battery
ages in standby mode. The reasons may be electrical cell leakages and a reduction
in chemical efficiency.
Aging affects each cell differently. Since the
cells are connected in series, controlling the individual cell voltages during
charge is virtually impossible. Even if the correct overall voltage is applied,
a weak cell will generate its own voltage level and intensify the condition further.
Much has been said about pulse charging lead-acid batteries. Some experts
believe there is a benefit in reduced cell corrosion but manufacturers and service
technicians are not in full agreement on the effectiveness. There are also disagreements
on the 'equalizing charge'. An equalizing charge raises the battery voltage for
several hours above that specified by the manufacturer. Although beneficial in
reversing sulfation, the side effects are elevated temperature, gassing and loss
of electrolyte if the service is not administered correctly. A periodic discharge
of about 10% is said to benefit the battery but little conclusive evidence is
available.
Lead-acid batteries must always be stored in a charged state.
A topping charge should be applied every six months to avoid the voltage from
dropping below 2.10V/cell on an SLA. Prolonged storage below the critical voltage
causes sulfation, a condition that is difficult to reverse. (See also: "How
to restore and prolong lead-acid batteries")
Charging
lead-acid batteries with a power supply
Lead-acid batteries can be
charged manually with a commercial power supply featuring voltage regulation and
current limiting. Calculate the charge voltage according to the number of cells
and desired voltage limit. Charging a 12-volt battery (6 cells) at a cell voltage
limit of 2.40V, for example, would require a voltage setting of 14.40V.
The charge current for small lead-acid batteries should be set between 10% and
30% of the rated capacity (30% of a 2Ah battery would be 600mA). Larger batteries,
such as those used in the automotive industry, are generally charged at lower
current ratings. Cells constructed of a non-antimonial lead grid material allow
higher charge currents but have a lower capacity. The cylindrical Cyclone is sealed
and can sustain a pressure of up to 3.5 Bar (50 psi). A pressurized cell assists
in the recombination of gases. Observe the battery temperature, voltage
and current during charge. Charge only at ambient temperatures and in a ventilated
room. Once the battery is fully charged and the current has dropped to 3% of the
rated current, the charge is completed. A good car battery will drop to about
40mA when fully charged; a bad battery may not fall below 100mA.
After
full charge, remove the battery from the charger. If float charge is needed for
operational readiness, lower the charge voltage to about 13.50V (2.25V/cell).
Most chargers perform this function automatically. The float charge can be applied
for an unlimited time.
State-of-charge
reading based on terminal voltage
The state-of-charge of a lead-acid battery can, to a certain extent,
be estimated by measuring the open terminal voltage. Prior to measuring,
the battery must have rested for 4-8 hours after charge or discharge
and resided at a steady room temperature. A cold battery would show
slightly higher voltages and a hot battery would be lower. Plate additions
of calcium and antimony will also vary the open terminal voltage with
calcium being a little higher than antimony. Furthermore, AGM has
a higher voltage plateau than the flooded lead acid and the readings
on Figure 3 may not apply for AGM systems. Due to surface charge,
a brief charge will raise the terminal voltage and provide inflated
state-of-charge reading. For example, a 30 minute charge could wrongly
indicate 100% SoC if no rest is applied.
With sufficient rest and stable temperature, voltage measurements
provide an amazingly accurate SoC estimation for lead acid batteries.
It is important that the battery is free of polarization. If connected
in a system, such as in a car, there are steady auxiliary loads, not
to mention frequent starting and driving.
Open
circuit voltage | State-of-Charge
in % | | Figure
3: BCI standard for SoC estimation of a 12V flooded lead acid car battery.
Test
the battery at room temperature. Allow 4-8 hour of rest after charge or discharge. Courtesy
of BCI |
12.65V | 100% | 12.45V | 75% | 12.24V | 50% | 12.06V | 25% | 11.89V
or less | Discharged | | | |
Note:
The BCI readings apply to flooded batteries with antimony doping.
Calcium will raise the voltage by 5 - 8%. Calcium is commonly used
for maintenance-free lead acid batteries.
After charge or discharge, allow the battery to rest for a minimum
of eight hours before assessing the state-of-charge by measuring the
terminal voltage.
Battery as a buffer
While dwelling on float-charge, an external load can be connected
to a lead-acid battery. In such a case, the battery acts as a buffer.
Micro-towers on cell sites work this way. During off-peak periods,
the batteries get fully charged. On peak traffic times, the load exceeds
the net supply provided by the rectifier (charger) and the battery
supplies the extra energy. A car battery works in a similar way.
When configuring a battery as a buffer, make certain that the battery
has the opportunity to fully charge between loads. The net charge
must be greater than what is drawn from the battery. Some chargers
switch to fast charge after a deep discharge, others simply use the
float charge to recharge. Allow up to 48 hours to fully recharge on
float charge. Deep discharges should be avoided if possible. Assure
that the float charge voltage is set correctly.
_________________________
Created: April 2003, Last edited: February 2007
About the Author Isidor Buchmann is the founder and CEO of Cadex Electronics
Inc., in Vancouver BC. Mr. Buchmann has a background in radio communications
and has studied the behavior of rechargeable batteries in practical, everyday
applications for two decades. Award winning author of many articles and books
on batteries, Mr. Buchmann has delivered technical papers around the world.
Cadex Electronics is a manufacturer of advanced battery chargers, battery analyzers
and PC software. For product information please visit www.cadex.com.
Click
here for a printer-friendly version
©
Copyright 2003 - 2005 Isidor Buchmann
| |